ISO 9001:2000 Certified Company |
|
|
Home »
Products » FRP Induced Draft Cooling Towers
FRP Induced Draft Cooling Towers
FRP Cooling Towers Induced type,
offered by Oceanic Cooling Towers Private Limited are known for superior
design and technology. The cooling towers are designed to meet the high
standard of performance demanded by engineers. These FRP induced draft
cooling towers deliver compact, heavy duty and efficient cooling function
and have an aesthetic design. Owing to its compactness, these FRP induced
cooling towers are extensively used in many process industries and in HVAC
applications.
 |
|
Material Selection
Casing
It has rust proof tough FRP bottle type design, which can withstand high
wind velocity and vibrations. This model does not require any painting and
is compact in design with long life.
Filling
Comes with a honeycomb designed rigid PVC, which has extended surface area.
It assists in splitting air and water, which in turn enhances the contact
time and heat transfer area through evaporation. Our PVC modules are vacuum
formed and comes with double edges, to provide highly efficient and robust
packing. These modules are the heart of cooling tower.
Fan
The fan of the module is aerodynamically designed & has adjustable
blade type axial. The flow fan is highly efficient & ensures large air
flow at low static pressure with low noise levels.
Motor
The motor used is squirell-cage TEFC induction motor, which comes with IP55
weather proof electric motor that is suitable for humid outdoor conditions.
Distribution
A special rotary aluminum alloy-sprinkler with sealed ball bearings is
specifically designed to take care of radial and thrust loads rotating at 5
to 7 R.P.M & distributing water through PVC branch pipes. It uniformally
sprays water on the PVC fills. SS-304 sprinklers are also available upon
clients request.
Few of the Salient Features of this machine are:
- Compact in size
- Light in weight
- Modular in design
- Lesser Make-Up
- Look Proof basin
- Easy to Install
- Durable in nature
- Prompt After Sales Service
- Long Life
|
- Corrosion Resistant
- Non-deteriorating
- Easily Maintainable
- Scientific Design
- Power Saving
- Possible roof top Installation
- Efficient
- Interchangeable Spares
|
| Model |
Nominal
Capacity TR |
Heat
Rejection / Kca / Hr X 1000 |
Overaall
Dimensions |
Fan Dia
mm |
Motor
HP |
Air
Flow CFM |
Operating
Weight (kg) |
Pump
Head mm H2O |
Height
mm |
Diameter
mm |
| OCT FRP -01-1 |
7.5 |
28 |
2000 |
1000 |
700 |
1.0 |
3600 |
250 |
2000 |
| OCT FRP -02-1 |
15 |
56 |
2000 |
1200 |
800 |
1.0 |
4000 |
320 |
2000 |
| OCT FRP -03-1 |
25 |
94 |
2100 |
1800 |
1000 |
2.0 |
8100 |
450 |
2400 |
| OCT FRP -04-1 |
30 |
113 |
2200 |
1800 |
1000 |
2.0 |
9000 |
500 |
2400 |
| OCT FRP -05-1 |
40 |
150 |
2500 |
2250 |
1250 |
2.0 |
12000 |
700 |
3000 |
| OCT FRP -06-1 |
50 |
189 |
2800 |
2250 |
1250 |
2.0 |
16000 |
800 |
3000 |
| OCT FRP -07-1 |
60 |
226 |
2800 |
2250 |
1250 |
3.0 |
18000 |
1300 |
3000 |
| OCT FRP -08-1 |
80 |
300 |
3000 |
2800 |
1500 |
3.0 |
22000 |
1500 |
3000 |
| OCT FRP -09-1 |
100 |
378 |
3000 |
2800 |
1500 |
5.0 |
24500 |
1500 |
3000 |
| OCT FRP -10-1 |
125 |
469 |
3000 |
3100 |
1500 |
5.0 |
29000 |
1700 |
3200 |
| OCT FRP -11-1 |
150 |
563 |
3000 |
3100 |
1500 |
7.5 |
40000 |
1800 |
3200 |
| OCT FRP -12-1 |
175 |
656 |
3200 |
3600 |
1800 |
7.5 |
32000 |
2100 |
3400 |
| OCT FRP -13-1 |
200 |
750 |
3200 |
3600 |
1800 |
10.0 |
40500 |
2300 |
3400 |
| OCT FRP -14-1 |
250 |
938 |
3500 |
4000 |
1800 |
10.0 |
42000 |
3000 |
3700 |
| OCT FRP -15-1 |
300 |
1126 |
3500 |
4000 |
1800 |
10.0 |
40000 |
3500 |
3700 |
| OCT FRP -16-1 |
400 |
1500 |
3700 |
5800 |
2400 |
15.0 |
55000 |
5500 |
4000 |
| OCT FRP -17-1 |
500 |
1876 |
4000 |
5800 |
3000 |
15.0 |
68000 |
6000 |
4300 |
OCT FRP -18-1
|
600 |
2252 |
4000 |
6600 |
3400 |
20.0 |
80000 |
7500 |
4500 |